| CBE-30A 1P | CBE-30A 2P | CBE-30A 3P |
|
Internal Working Diagram |
Type |
CBE-30 |
|
Standard |
GB17701-1999 |
|
|
Rated voltage |
DC65V,AC250V |
|
|
Rated current |
1-30A |
|
|
Rated short-circuit breaker capacity |
DC65V, 2200A |
|
|
AC 50Hz, 250V, 2500A |
||
|
O-t-co |
||
|
Insulated resistance |
500V, 10OM Ω (cold) |
|
|
Frequnecy compression |
50Hz 2500V, 60s |
|
|
Life |
Mechamical life 1000 times |
|
|
Electrical life 6000 times |
||
|
Environment temperature |
-40℃ 〜+85℃ |
|
|
Low at mospheric pressurre |
5.85x10³Pa (439mmHg) |
|
|
Vibration resistance |
10 〜55Hz 1.5mm |
|
|
28 〜55Hz5g |
||
|
Impact resistance |
Acceleration of impact resistance 50g, the width of mparse 11 ms, impulse shape: half-shine wave. |
|
|
Times of impact 18 times (each direction 3 times) |
||
|
The direction of impact: X, Y, Z, six directions |
||
|
Poles |
1 ~ 3 poles |
|
|
Connection mode |
Bolt screw insert and pumout |
| CBE-30B 1P | CBE-30B 2P | CBE-50A 1P | CBE-50A 2P | CBE-50A 3P | CBE-50B 1P |
Specification
|
Type |
CBE-50 |
|
Standard |
GB17701-1999 |
|
Rated voltage |
DC65V,AC250V |
|
Rated current |
1-50A |
|
Rated short-circuit breaker capacity |
DC65V, 2200A |
|
AC 50Hz, 250V, 2500A |
|
|
o-t-co |
|
|
Insulated resistance |
500V, 100M Ω (cold) |
|
Frequnecy compression |
50Hz 2500V, 60s |
|
Life |
Mechamical life 1000 times |
|
Electrical life 8000 times |
|
|
Environment temperature |
-40℃ 〜+85℃ |
|
Low at mospheric pressurre |
5.85x10³Pa (439mmHg) |
|
Vibration resistance |
10 〜55Hz 1.5mm |
|
28 〜55Hz5g |
|
|
Impact resistance |
Acceleration of impact resistance 50g, the width of mparse 11 ms, impulse shape: half-shine wave. |
|
Times of impact 18 times (each direction 3 times) |
|
|
The direction of impact: X, Y, Z, six directions |
|
|
Poles |
1 ~ 3 poles |
|
Connection mode |
Bolt screw insert and pumout |
Characteristic Curve